A2L Refrigerants: What Commercial Kitchen Operators Need to Know

Last fact-checked: July 22, 2026

A2L is a refrigerant safety classification, not a product. It covers refrigerants with lower toxicity and lower flammability. A2Ls are becoming common in new commercial air conditioning and in some refrigeration equipment, but they are one of several lower-GWP options a commercial kitchen will meet. In May 2026 the EPA moved several of the compliance dates that had been set for January 2026, which means a good deal of what has been published about this transition is now out of date.

The three things that matter

  • What changed: the EPA’s May 2026 rule sets an interim limit of 1,400 global warming potential for remote condensing units from July 27, 2026, and for supermarket systems from January 1, 2027. Both run until January 1, 2032. Cold storage warehouses get an interim limit of 700 from July 27, 2026.
  • What did not change: the production and consumption phasedown. The cap on how much HFC refrigerant can be made or imported in the United States drops from 60 percent of baseline to 30 percent in 2029.
  • What you have to do right now: no federal rule requires you to replace working equipment. These rules restrict what can be manufactured, imported and newly installed, so this matters when you are buying, not when you are operating.

This covers United States federal refrigerant rules. State and local mechanical, fire and building codes, your equipment listings and manufacturer requirements can all add restrictions on top of them.

The May 2026 rule is also being challenged in federal court, and one of those challenges targets its effective date. The dates below reflect the rule as finalized and were checked on July 22, 2026.

On this page

What is an A2L refrigerant?

A2L is a safety group under ASHRAE Standard 34, the standard that classifies refrigerants by toxicity and flammability. The letter A means lower toxicity. The 2L means lower flammability.

To be classed 2L a refrigerant has to meet four criteria: it shows flame propagation when tested, its lower flammability limit is above 0.10 kilograms per cubic meter, its heat of combustion is below 19,000 kilojoules per kilogram, and its maximum burning velocity is 10 centimeters per second or lower when tested in dry air at 23 degrees Celsius and normal atmospheric pressure.

That burning velocity ceiling is the part that shapes how the equipment is built. An A2L refrigerant can ignite, but flame travels through it slowly enough that the engineering answer is leak detection and ventilation rather than keeping it out of buildings. The full flammability ladder runs A1, A2L, A2 and A3. R-410A and R-404A are A1, which will not ignite under normal conditions. Propane is A3, the higher flammability group.

A2L refrigerants are a mix of chemistries. Some are hydrofluoroolefins, or HFOs. Some are hydrofluorocarbons: R-32 is an HFC and is classified A2L in its own right. Many are blends of both, and R-454B is roughly two thirds R-32 by weight. HFO components generally break down in the atmosphere far faster than the older HFCs they replace, which is what pulls a blend’s global warming potential down. Flammability is assessed separately, through the ASHRAE classification, rather than following automatically from that chemistry.

Global warming potential, or GWP, compares a gas against carbon dioxide over a set period, normally 100 years. Carbon dioxide is 1. R-404A is 3,922. Every GWP figure on this page uses the IPCC Fourth Assessment Report values, because those are the ones the AIM Act and EPA’s regulations actually run on. Other assessment reports give different numbers for the same refrigerants, which is worth knowing if you are comparing figures from another source.

GWP is also a different measure from ozone depletion potential, which is what drove the R-22 phase-out that most kitchens went through years ago. The current rules are about warming, not the ozone layer, which is why refrigerants that were perfectly acceptable in 2015 are being restricted now.

What changed in 2026

On May 21, 2026 the EPA finalized a rule revising its 2023 Technology Transitions Rule. It was published in the Federal Register on May 26, 2026 at 91 Fed. Reg. 31284 and takes effect on July 27, 2026. The revision extended several compliance dates and raised the interim GWP limits that apply until those dates arrive.

Equipment category Under the 2023 rule After the May 2026 rule Interim limit starts
Remote condensing units, which covers most walk-in coolers and freezers 150 or 300 GWP from January 1, 2026 Interim limit of 1,400 GWP until January 1, 2032 July 27, 2026
Supermarket systems 150 or 300 GWP from January 1, 2027 Interim limit of 1,400 GWP until January 1, 2032 January 1, 2027
Cold storage warehouses From January 1, 2026 Interim limit of 700 GWP until January 1, 2032 July 27, 2026
Residential and light commercial air conditioning and heat pumps 700 GWP on equipment made or imported from January 1, 2025, with a deadline to install existing stock Installation deadline removed for units made or imported before January 1, 2025 July 27, 2026
Stand-alone and self-contained retail food refrigeration 150 GWP from January 1, 2025 Unchanged Already in force

Where two numbers appear, the 150 limit applies to systems holding 200 pounds of refrigerant or more, and the 300 limit applies to smaller systems and to the high temperature side of a cascade system.

Two things did not move. The final GWP limits are the same, so the destination has not changed, only the road to it. And the HFC production and consumption phasedown was left alone entirely, which matters more than the delay does. More on that in the next section.

The rule is also not settled. Several petitions are pending in the U.S. Court of Appeals for the D.C. Circuit. Two were filed on June 25, 2026 by HVACR trade associations, one covering remote condensing units and supermarket systems and the other also reaching cold storage. A coalition of 19 state attorneys general and New York City filed on July 21, 2026, and the Natural Resources Defense Council has filed separately. The petitioners argue variously that the rule is arbitrary and capricious, that it conflicts with the AIM Act, and that the AIM Act’s one-year waiting period makes the rule’s 60-day effective date unlawful. That last point matters here: one of the pending challenges is aimed squarely at the July 27 date. Anyone making a long-term equipment decision should check where the litigation stands rather than treat these dates as fixed.

Does the delay keep R-404A eligible for new equipment?

Generally no. R-404A has a GWP of 3,922, which is well above the 1,400 interim limit and further still above the 150 and 300 limits that arrive in 2032. What the delay actually does is keep lower-GWP A1 blends such as R-448A and R-449A available for new remote refrigeration systems for several more years. It does not open a path to buying new R-404A equipment.

Existing R-404A systems are a separate matter. They can keep running, and they can still be serviced with the refrigerant they were built for. Components sold for that purpose are labeled for servicing existing equipment only.

The more useful question is what that refrigerant will cost and whether it will be there, because the EPA did not touch the rule that controls how much of it gets made.

Two different rules are at work here and they are easy to confuse.

The Technology Transitions Rule governs what equipment can be manufactured, imported and newly installed. That is the one that moved in May 2026.

The production and consumption phasedown under the AIM Act of 2020 governs how much hydrofluorocarbon refrigerant can be produced or imported in the United States at all. That one is unchanged, and it steps down on a fixed schedule: 60 percent of baseline from 2024 through 2028, 30 percent from 2029 through 2033, 20 percent from 2034 through 2035, and 15 percent from 2036 onward. The overall target is an 85 percent reduction by 2036.

The 2029 step is the steepest still ahead. The allowance cap falls by half, from 60 percent of baseline to 30. EPA’s own analysis projects that demand for newly produced or imported HFCs will exceed the quantity available to allocate around that 2029 step down, absent other measures.

Set that against how long this equipment lasts. A walk-in condensing unit bought in 2026 is very likely still running in 2036. For most of that service life, the refrigerant inside it will be under a cap that keeps tightening. So the useful question is not what your compliance deadline is. It is what you expect to pay for a refrigerant charge in year seven of that unit’s life, and whether it will be readily available when a technician needs it on a Friday afternoon.

We are not going to put a number on future refrigerant prices, because nobody can do that credibly. Reclaimed refrigerant, existing inventories and market behavior all affect what is actually available. What can be said is that the direction is set by a published schedule rather than by the market, and that the delay announced in May does not change it.

Which refrigerants you will actually see in a commercial kitchen

Three families, depending on the equipment.

Where you meet it Refrigerant Safety class Often used instead of
Rooftop units, split systems, packaged HVAC R-454B, often written R454B, and R-32 A2L R-410A
Walk-in coolers and freezers, remote condensing systems R-455A, R-454C A2L R-404A
Equipment built to the interim 1,400 limit R-448A, R-449A A1 R-404A
Medium temperature equipment R-513A A1 R-134a
Reach-ins, undercounters, prep tables, merchandisers, many newer self-contained ice machines R-290 A3 R-404A, R-134a
Large refrigeration racks and cold storage R-744, which is carbon dioxide A1 R-404A

These are examples of what equipment is being built with, not drop-in substitutions. Which refrigerant is right depends on the equipment type, operating temperature, charge size, system design, manufacturer approval and local code. None of the A2Ls listed here is a retrofit refrigerant for an existing system.

The third row is worth noticing. The interim limit of 1,400 does not require an A2L at all. R-448A and R-449A are A1, they are already widely used, and equipment built around them is what the extended deadline permits. That is the practical effect of the May 2026 rule for walk-in refrigeration.

The R-290 row is the one most operators are surprised by, and it gets its own section.

Is R-290 an A2L refrigerant?

No. R-290 is propane, and it is classified A3, the higher flammability group. It is not an A2L, and it is governed by a different set of limits.

R-290 has a GWP of about 3, against R-404A’s 3,922, which is why it has spread so quickly through self-contained foodservice equipment. Because it is an A3, the safety approach is to limit how much of it any one appliance contains. Under EPA SNAP Rule 26, effective in July 2024, qualifying self-contained equipment may hold roughly 300 grams of R-290 per circuit in a closed case with doors or drawers, and roughly 500 grams per circuit in an open case such as a merchandiser. The precise ceilings are set as multiples of the refrigerant’s lower flammability limit, which works out to 304 grams and 494 grams. A lower limit of about 114 grams applies in public corridors and lobbies. The previous ceiling was 150 grams.

These are not blanket allowances. They apply to equipment designed and listed to UL 60335-2-89, not to older listings, and the equipment has to be built for the charge it carries.

That change is why R-290 turned up in more of your kitchen than you may realize. At 150 grams, propane was limited to small equipment. At the higher limits, manufacturers can build full-size reach-ins, prep tables and merchandisers on a single circuit.

Manufacturers have taken different routes to it. Beverage-Air has moved nearly its whole foodservice refrigeration line to hydrocarbons, mostly R-290, with some merchandisers on R-600a. Hoshizaki’s Steelheart series runs on R-290 across reach-ins, freezers, prep tables and pass-thrus. Traulsen offers both, and the dividing line on current models is that self-contained units use R-290 while remote applications do not. Manitowoc’s Indigo NXT is a platform rather than a single refrigerant: the iP-series models are R-290, while other Indigo NXT models ship with R-410A or R-404A, so the model prefix decides what you have.

That variation is the reason to check rather than assume. If you have bought a reach-in, an undercounter unit or a self-contained ice machine in the last two or three years, look at the nameplate. There is a fair chance it runs on propane. It will be labeled, and the charge will be small enough that the appliance was listed as safe for indoor use at that charge.

What A2L changes about getting your equipment serviced

The main change is that on larger-charge equipment, leak detection is built into the appliance rather than added to the room.

For commercial refrigeration this is set by UL 60335-2-89, the safety standard these units are listed to. The requirement scales with the refrigerant charge, the refrigerant’s lower flammability limit and the volume of the room, so larger-charge equipment carries a refrigerant detection system as part of its listing while smaller self-contained units can comply through charge limits and construction instead. Where a detection system is fitted and the sensor detects a leak, the unit responds on its own, typically by shutting down the compressor and running fans to disperse the refrigerant.

Three practical consequences for an operator.

Any factory-fitted refrigerant sensor, fan control or shutoff is part of the equipment’s safety design and must not be disabled or bypassed, including during service. If a unit is nuisance-tripping, that is a fault to diagnose, not a sensor to unplug.

Where a unit has a sensor, it has a service life and eventually needs replacing. Follow the manufacturer’s inspection and replacement schedule, and on a unit under a maintenance agreement track it the same way you track filters and belts.

Servicing an A2L or R-290 system requires tools rated for it, including recovery equipment, gauges and hoses, and refrigerants are not interchangeable between systems. Topping up an A2L unit with whatever is on the truck is not an option.

One thing worth asking any contractor directly. EPA Section 608 certification is required for technicians handling most refrigerants, though not all: EPA exempts certain substitutes in specific end uses, and that exemption covers R-290 in stand-alone retail food refrigerators and freezers and in self-contained commercial ice machines, as well as carbon dioxide. More to the point, a 608 card on its own is not evidence that a technician is trained and equipped for A2L or R-290 work. That is a fair question to ask before someone opens a unit in your kitchen.

Can existing equipment be converted to A2L?

No.

EPA lists these refrigerants as acceptable only in equipment specifically designed for them. Charging an A2L into a system that was not listed for it breaches the conditions of that listing, puts the equipment outside the standard it was built and certified to, and removes the safety features the classification assumes are present: the leak detection where it is required, the automatic response to a leak, and the selection of electrical components so they are not ignition sources.

What you can do is keep running what you have. Existing R-404A and R-410A equipment continues to operate on the refrigerant it was designed for, and it can be serviced with that refrigerant. If a particular system does need a refrigerant change for some other reason, there are A1 blends intended for that purpose, though they are rarely a straight swap and usually require checking oil compatibility, valves, controls, capacity and discharge temperature. That is a conversation to have about the specific unit rather than as a blanket policy.

What to do in the next twelve months

Build a refrigerant inventory. That is the entire action, and for most single-site kitchens it takes an afternoon.

Walk the site with a notepad and record three things off the data plate of every piece of refrigeration and HVAC equipment you own:

  1. The refrigerant it uses. It is printed on the nameplate or data plate, usually on the back or inside the door of self-contained units, and on the condensing unit for a walk-in.
  2. The age of the unit and roughly how much service life you expect from it.
  3. The charge size, where the plate lists it.

Then sort the list. Anything running R-404A or R-410A that you expect to keep for more than about five years is where your exposure sits, because that equipment will spend most of its remaining life drawing on a refrigerant supply that is being capped down. Those units are the ones to think about in a capital plan, in the order their service lives run out.

Nothing on that list needs replacing because of a deadline. The point of the inventory is that when a unit does fail, or when it comes up for planned replacement, you already know what you are holding and you are making that decision on a normal schedule instead of during a breakdown.

What not to do

Do not let anyone top off a system from an unlabeled cylinder. As supply tightens, mislabeled and counterfeit refrigerant becomes a real problem, and the damage from the wrong refrigerant in a system is expensive and sometimes dangerous.

Do not buy refrigerant from an unverified source on price. The same reason.

Do not assume a Section 608 card means a technician is ready for A2L or R-290 work. Ask.

Do not replace working equipment because of a headline about a deadline. Check whether the rule actually applies to what you own. For most commercial kitchens the answer today is that it applies to your next purchase, not to your current equipment.

Frequently asked questions

What does A2L mean?

A2L is a refrigerant safety group under ASHRAE Standard 34. The A means lower toxicity. The 2L means lower flammability, which requires flame propagation on testing, a lower flammability limit above 0.10 kilograms per cubic meter, a heat of combustion below 19,000 kilojoules per kilogram, and a maximum burning velocity of 10 centimeters per second or lower in dry air.

Is A2L refrigerant flammable?

Yes, mildly. It can ignite, but flame moves through it slowly enough to be classed 2L, which is why larger-charge equipment using it carries built-in leak detection rather than being kept out of occupied buildings.

Did the EPA delay the refrigerant rules?

Yes. A final rule announced May 21, 2026 and effective July 27, 2026 sets an interim limit of 1,400 GWP for remote condensing units from July 27, 2026 and for supermarket systems from January 1, 2027, both until January 1, 2032, and 700 for cold storage warehouses from July 27, 2026.

Do I have to replace my existing refrigeration equipment?

No. These rules restrict what may be manufactured, imported and newly installed. They do not require anyone to remove equipment that is working.

What refrigerant replaces R-404A?

There is no single replacement. It depends on the equipment: R-455A and R-454C in purpose-built remote systems, R-448A and R-449A as A1 blends that meet the interim 1,400 limit, R-290 in self-contained equipment, and CO2 in large racks and cold storage.

What refrigerant replaces R-410A?

R-454B and R-32 are the common choices in new packaged and split air conditioning. Neither is a retrofit refrigerant for an existing R-410A system.

Can R-404A or R-410A equipment be converted to A2L?

No. EPA lists these refrigerants as acceptable only in equipment specifically designed for them, so charging one into a system not built for it breaches those conditions and puts the equipment outside its listing.

Is R-290 an A2L refrigerant?

No. R-290 is propane, classified A3, with a GWP of about 3. It carries its own charge limits, roughly 300 grams per circuit in closed appliances and roughly 500 grams in open ones, with a lower limit in public corridors and lobbies.

Will R-404A still be available for my existing equipment?

It remains legal to service existing systems with R-404A, and components are sold labeled for that purpose. Future supply and pricing are less certain: the production and consumption cap steps down from 60 percent of baseline to 30 percent in 2029, and EPA’s own analysis projects demand exceeding the quantity available to allocate around that step down.

How do I find out what refrigerant my equipment uses?

It is printed on the nameplate or data plate. On self-contained units it is usually on the back or inside the door. On a walk-in it is on the condensing unit.